Thanks to its excellent breaking capacity and compact dimensions, the Compact NS80H MA circuit-breaker is specially designed to satisfy specific motor protection needs up to 37 kW.  Compact NS80H MA:the guarantee of absolute peace of mind.
Applications
Device dedicated to protection of motors from 0.37 kW to 37 kW.
Discovery
 

80 A moulded case circuit-breakers for motor protection

   
 
Description
  • Nominal current:80 A
  • Breaking performance:70 kA at 380/415 V
  • Voltage rating:690 V
  • 3-pole version
  • Installation on mounting plate or DIN rail
  • Built-in magnetic trip unit
  • Instantaneous protection adjustable from 6 to 14 In
  • Indication and control accessories and auxiliaries
  • Type 2 co-ordination as per IEC 60947-4
  • Compliance with international standard IEC 60947-2