 Benefits
For more simplicity, the motor protection cicuit breaker P25M is designed for installation in modular final distribution enclosures.
Applications
- Motor protection in all industrial and tertiary buildings.
| |
| | | |
| |
Description
- Rating current:0,16 to 25A
- Breaking capacities:15kA under 400/415 V
- Thermal trip:sensitive to underphase; magnetic trip:12 In
- Compliance with standards:IEC 60947-2, IEC 60947-4-1, certified by national official authorities
- Suitable for isolation in accordance with industrial standards:IEC 60947
- Operating voltage:up to 690Vac, insulation voltage:690V
- Optional add-on limiting unit:breaking power increased to 100 kA under 400/415V
- Optional auxiliaries:indication of state and tripping, shunt trip, undervoltage trip
| |
| | | |
| |  P25M circuit-breaker

Add-on limiting unit
|